🚨 Informamos aos concluintes que após a validação do orientador no sistema, A BIBLIOTECA PRECISA DE 7 DIAS ÚTEIS para tratar e processar os dados. Por isso, NÃO DEIXE PARA ENVIAR O TCC (graduação ou pós-graduação) DE ÚLTIMA HORA. Dúvidas: repositorio@ufersa.edu.br🚨

Impacto do posicionamento de geração distribuída em redes de distribuição: análise de potência ativa, perdas ativas e tensão em um alimentador real de Mossoró-RN

dc.contributor.advisorRocha, Ednardo Pereira da
dc.contributor.advisormailednardo.pereira@ufersa.edu.br
dc.contributor.authorSilva, Jackson Angell Alves e
dc.contributor.coadvisorSilva, Rogerio Diogne de Souza e
dc.contributor.referee1Rocha, Ednardo Pereira da
dc.contributor.referee2Silva, Rogerio Diogne de Souza e
dc.contributor.referee3Moura, Adriano Aron Freitas de
dc.contributor.referee4Fonseca, Jonatha Revoredo Leite da
dc.coverage.spatialMossoró
dc.date.accessioned2025-07-01T16:54:18Z
dc.date.available2025-07-01T16:54:18Z
dc.date.issued2025-03-28
dc.description.abstractA crescente inserção da Geração Distribuída (GD) tem transformado as Redes de Distribuição de Energia Elétrica (RDEE) mudando sua topologia clássica, trazendo a principio benefícios como redução de perdas, alívio do carregamento dos alimentadores e estabilidade na tensão. No entanto, com o aumento penetração GD nas redes de distribuição sem planejamento adequado que considere os locais de instalação e a quantidade de potência de geração geram impactos negativos, como: inversão do fluxo de potência no alimentador, aumento nas perdas ativas e elevação de tensão para além dos limites regulatórios. Este trabalho tem como objetivo analisar o impacto da GD em uma rede de distribuição real localizada em Mossoró-RN, avaliando seus efeitos sobre potência ativa no alimentador, perdas ativas e variação de tensão. Para isso, foram desenvolvidos quatro cenários distintos com quantidades e posicionamento variados da GD, variando os níveis de carregamento em 30%, 50%, 70% e 90%. Para cada carregamento foi realizado uma injeção de potência na rede variando de 0 a 4.400 kW, utilizando o software OpenDSS em conjunto com Pyhton para as simulações de cada cenário. Os resultados indicam que tanto a posição da GD como sua potência têm influência direta nos níveis de tensão, nas perdas que apresenta comportamento de redução ou aumento, variando com os cenários propostos. Sendo a distribuição de quatro geradores tanto na parte mediana quando nos finais de trecho do circuito estudado apresentaram o melhor desempenho comparando com a injeção concentrada em um único local. O estudo contribui para a definição de diretrizes para a alocação estratégica de GD, auxiliando concessionárias e formuladores de políticas na mitigação de impactos adversos e otimização da operação da rede.
dc.description.abstract2The increasing integration of Distributed Generation (DG) has transformed Distribution Networks (DN), changing their classic topology, bringing benefits such as loss reduction, feeder load relief and voltage stability. However, with the inadequate allocation of DG, considering the installation sites and the amount of generation power, it can generate negative impacts, such as the inversion of the power flow in the feeder, an increase in active losses and a voltage rise beyond the regulatory limits. This work aims to analyze the impact of DG on a real distribution network located in Mossoró-RN, evaluating its effects on active power in the feeder, active losses and voltage variation. To this end, four different scenarios were developed with varying amounts and positioning of DG, varying the load levels by 30%, 50%, 70% and 90%. Power was injected into the grid for each load, ranging from 0 to 4,400 kW, using OpenDSS software in conjunction with Pyhton for the simulations of each scenario. The results indicate that both the position of the DG and its power have a direct influence on voltage levels and losses, which show a decrease and increase depending on the scenario. The distribution of the four generators in the center of the circuit or at the end of the grid showed the best performance compared to concentration at a single point. The study contributes to defining guidelines for the strategic allocation of DG, helping utilities and policymakers to mitigate adverse impacts and optimize grid operation.
dc.description.physical117 f. : il.
dc.format.mimetypepdf
dc.identifier.advisorLatteshttp://lattes.cnpq.br/8754856801344344
dc.identifier.authorLatteshttp://lattes.cnpq.br/5986775562089447
dc.identifier.bibliographicCitationSILVA, Jackson Angell Alves e. Impacto do Posicionamento de Geração Distribuída em Redes de Distribuição: análise de potência ativa, perdas ativas e tensão em um alimentador real de Mossoró-RN. 2025. 117 f. Dissertação (Mestrado em Engenharia Elétrica) - Universidade Federal Rural do Semi-Árido, Mossoró, 2025.
dc.identifier.coadvisorLatteshttp://lattes.cnpq.br/7704979218417437
dc.identifier.urihttps://repositorio.ufersa.edu.br/handle/prefix/13354
dc.language.isopt_BR
dc.publisher.centerCentro de Engenharias - CE
dc.publisher.countryBrasil
dc.publisher.initialsUFERSA
dc.publisher.institutionUniversidade Federal Rural do Semi-Árido
dc.publisher.programPrograma de Pós-Graduação em Engenharia Elétrica
dc.rightsinfo:eu-repo/semantics/openAccess
dc.rights.holderUFERSA
dc.rights.licenseAttribution-ShareAlike 3.0 Brazilen
dc.rights.urihttp://creativecommons.org/licenses/by-sa/3.0/br/
dc.subject.cnpqENGENHARIAS::ENGENHARIA ELETRICA
dc.subject.keywordGeração distribuída
dc.subject.keywordRedes de distribuição
dc.subject.keywordPerdas elétricas
dc.subject.keywordEstabilidade de tensão
dc.subject.keywordOpenDSS
dc.subject.keywordDistributed generation
dc.subject.keywordDistribution networks
dc.subject.keywordElectrical losses
dc.subject.keywordVoltage stability
dc.subject.keywordOpenDSS
dc.titleImpacto do posicionamento de geração distribuída em redes de distribuição: análise de potência ativa, perdas ativas e tensão em um alimentador real de Mossoró-RN
dc.title.alternativeImpact of distributed generation positioning on distribution networks: analysis of active power, active losses, and voltage in a real feeder in Mossoró, Rio Grande do Norte
dc.typeinfo:eu-repo/semantics/masterThesis

Arquivos

Pacote original

Agora exibindo 1 - 1 de 1
Carregando...
Imagem de Miniatura
Nome:
JacksonAAS - DISSERTAÇÃO.pdf
Tamanho:
3,73 MB
Formato:
Adobe Portable Document Format

Licença do pacote

Agora exibindo 1 - 1 de 1
Carregando...
Imagem de Miniatura
Nome:
license.txt
Tamanho:
1,58 KB
Formato:
Item-specific license agreed upon to submission
Descrição: