Integração de turbinas eólicas tipo IV à rede elétrica: Simulação e Análise usando o ATPDraw
| dc.contributor.advisor | Moura, Adriano Aron Freitas de | |
| dc.contributor.author | Oliveira, Max Brazão de | |
| dc.contributor.coadvisor | Aguiar, Victor de Paula Brandão | |
| dc.contributor.referee1 | Moura , Adriano Aron Freitas de | |
| dc.contributor.referee2 | Aguiar, Victor de Paula Brandão | |
| dc.contributor.referee3 | Rocha, Ednardo Pereira da | |
| dc.contributor.referee4 | Queiroz Júnior, Idalmi de Souza | |
| dc.coverage.spatial | Mossoró | |
| dc.date.accessioned | 2024-01-10T15:36:03Z | |
| dc.date.available | 2024-01-10T15:36:03Z | |
| dc.date.issued | 2023-10-09 | |
| dc.description.abstract | Neste estudo foram realizadas simulações operando o software ATPDraw com o propósito de analisar uma turbina eólica do tipo IV e a sua integração com à rede. A arquitetura da turbina é composta por uma estrutura dividida em três partes. São elas; o retificador trifásico não controlado, o conversor boost e um inversor trifásico controlado alimentada por uma máquina síncrona. O resultado desse trabalho, acabou gerando alguns gráficos fruto da simulação de um gerador de 2,24 MVA acoplado a uma turbina eólica de tipo IV. Nas correntes trifásicas que serão injetadas na rede elétrica de transmissão, foi constatado que seus valores são compatíveis com os esperados, além das correntes estarem balanceada, e também foi constatado que o ângulos entre as fases é de 120°. As três correntes apresentaram valores elevados logo após o acionamento do aerogerador, e depois de um leve amortecimento em 0,03 segundos, logo após conseguiram se estabilizar em torno de 1 kA. O aerogerador atuou numa frequência de 60 Hz. Em relação à tensão no barramento do retificador, vimos que a curva que a descreve cresce rapidamente nos primeiros 0,3 segundos de simulação, depois de alcançar seu valor máximo, que chegou a 3,5 kV, se estabiliza abaixo de 3 kV. Essa tensão do barramento capacitivo será direcionado para o conversor boost, que vai agir como um elevador de tensão. Esse valor foi atingido após 0,90 segundos de simulação. As potências ativa e reativa que saem do inversor e são fornecidas à rede nos mostram que no princípio da simulação, o gerador está absorvendo potência, atuando próximo do comportamento de um motor, o que se revela pelos valores negativos nos gráficos. Há também uma oscilação nas potências, devido aos harmônicos presentes no circuito. A transição do regime transitório para o permanente ocorre somente depois de 1,25 segundos. O conversor não consegue compensar totalmente a potência reativa da rede, resultando em um fator de potência menor que um. A entregar da potência máxima ocorre 1,0 segundo após o acionamento da turbina, alcançando 1,5 MW. | |
| dc.description.abstract2 | In this study, simulations were carried out using the ATPDraw software with the purpose of analyzing a type IV wind turbine and its integration with the grid. The turbine architecture is made up of a structure divided into three parts. Are they; the uncontrolled three-phase rectifier, the boost converter and a controlled three-phase inverter fed by a synchronous machine. The result of this work ended up generating some graphics resulting from the simulation of a 2.24 MVA generator coupled to a type IV wind turbine. In the three-phase currents that will be injected into the electrical transmission network, it was found that their values are compatible with those expected, in addition to the currents being balanced, and it was also found that the angles between the phases are 120°. The three currents showed high values immediately after starting the wind turbine, and after a slight damping in 0.03 seconds, they managed to stabilize at around 1 kA. The wind turbine operated at a frequency of 60 Hz. Regarding the voltage on the rectifier bus, we saw that the curve that describes it grows quickly in the first 0.3 seconds of simulation, after reaching its maximum value, which reached 3.5 kV , stabilizes below 3 kV. This voltage from the capacitive bus will be directed to the boost converter, which will act as a voltage elevator. This value was reached after 0.90 seconds of simulation. The active and reactive powers that leave the inverter and are supplied to the grid show us that at the beginning of the simulation, the generator is absorbing power, acting close to the behavior of a motor, which is revealed by the negative values in the graphs. There is also an oscillation in powers, due to the harmonics present in the circuit. The transition from the transient to the permanent regime only occurs after 1.25 seconds. The converter cannot fully compensate the reactive power of the grid, resulting in a power factor of less than one. Maximum power is delivered 1.0 seconds after the turbine is activated, reaching 1.5 MW. | |
| dc.description.physical | 10 f. | |
| dc.format.mimetype | ||
| dc.identifier.bibliographicCitation | OLIVEIRA, Max Brazão de. Integração de turbinas eólicas tipo IV à rede elétrica: Simulação e Análise usando o ATPDraw. 2023. 10 f. TCC (Graduação) - Curso de Engenharia Elétrica, Centro de Engenharias - CE, Universidade Federal Rural do Semi-Árido - UFERSA, Mossoró/RN, 2023. | |
| dc.identifier.uri | https://repositorio.ufersa.edu.br/handle/prefix/10023 | |
| dc.language.iso | pt_BR | |
| dc.publisher.center | Centro de Engenharias - CE | |
| dc.publisher.country | Brasil | |
| dc.publisher.initials | UFERSA | |
| dc.publisher.institution | Universidade Federal Rural do Semi-Árido | |
| dc.rights | info:eu-repo/semantics/openAccess | en |
| dc.rights.holder | UFERSA | |
| dc.rights.uri | http://creativecommons.org/licenses/by-sa/3.0/br/ | |
| dc.subject.cnpq | ENGENHARIAS::ENGENHARIA ELETRICA | |
| dc.subject.keyword | Conversor Boost | |
| dc.subject.keyword | Energia eólica | |
| dc.subject.keyword | Simulação | |
| dc.subject.keyword | Rede elétrica | |
| dc.title | Integração de turbinas eólicas tipo IV à rede elétrica: Simulação e Análise usando o ATPDraw | |
| dc.type | info:eu-repo/semantics/bachelorThesis |