🚨 Informamos aos concluintes que após a validação do orientador no sistema, A BIBLIOTECA PRECISA DE 7 DIAS ÚTEIS para tratar e processar os dados. Por isso, NÃO DEIXE PARA ENVIAR O TCC (graduação ou pós-graduação) DE ÚLTIMA HORA. Dúvidas: repositorio@ufersa.edu.br🚨

Estudo de aterramento da usina fotovoltaica da UFERSA

Loading...
Thumbnail Image

Journal Title

Journal ISSN

Volume Title

Publisher

Abstract

The proposed work consists in verifying the ground conditions, as well as the ground resistance values of a grid-connected photovoltaic system located in UFERSA. The system consists of 580 photovoltaic modules, distributed in 5 strings having 116 modules each, and containing individual grounding. Visual inspection of ground conditions was carried out, and with the help of a terrometer using the Wenner method, ground resistance measurements were performed, obtaining values measured above 20 Ω. These values differ from those described in standards. Therefore, it was possible to conclude that the values of earth resistance are high, if compared to the current norm in Brazil, as well as international standards, and that some constructive aspects of grounding are in disagreement with what is described in standard, and in the solar power plant project



Description

Citation

Endorsement

Review

Supplemented By

Referenced By

Creative Commons license

Except where otherwise noted, this item's license is described as CC-BY-SA