Avaliação das condições de integridade e disponibilidade do sistema de combate a incêndio de um condomínio residencial após falha: corrosão na rede de hidrantes e funcionalidade do sistema de recalque

dc.contributor.advisorSilva, Marta Ligia Pereira da
dc.contributor.advisormailmartaligia@ufersa.edu.br
dc.contributor.authorSilva, Victor Esaú Carlos da
dc.contributor.coadvisorGomes, Kalyanne Keyly Pereira
dc.contributor.referee1Silva, Marta Ligia Pereira da
dc.contributor.referee2Gomes, Kalyanne Keyly Pereira
dc.contributor.referee3Oliveira, Tiago Fernandes de
dc.coverage.spatialMossoró
dc.date.accessioned2025-08-18T17:58:05Z
dc.date.available2025-08-18T17:58:05Z
dc.date.issued2025-08-05
dc.description.abstractEste trabalho aborda a inspeção em um sistema de combate a incêndio (SCI) de um edifício residencial localizado no bairro Costa e Silva em Mossoró -RN, tendo como base um caso real de falha, nesse condomínio, no acionamento do sistema durante um incêndio em um dos apartamentos. O objetivo principal foi identificar as causas da falha de funcionamento e verificar a existência de corrosão na rede pressurizada e nos componentes como: bomba de recalque, quadros de comando, tubulações e qualidade da água aprisionada nas tubulações. Para maiores evidencias nos resultados, foi realizada uma análise qualitativa e quantitativa da presença de íons de ferro e de óxidos de ferro Fe₂O₃ em amostras de água que foram coletadas da rede de hidrantes, confirmando a ocorrência de corrosão interna nas tubulações. Como resultado, foram identificados os fatores que levaram o sistema a falha e implementadas ações corretivas e preventivas, como manutenção nos equipamentos danificados, otimização com a instalação de sinalizadores de acionamento da bomba de recalque, alertas sonoros de nível e a implementação de testes periódicos de disponibilidade do sistema. A conclusão do estudo trouxe benefícios materiais como o retorno do pleno funcionamento do SCI e imateriais como o conhecimento adquirido ao ser realizado esse estudo, evidenciou também a importância de inspeções periódicas em sistemas de SCI e sugeriu levantamento para adoção futura de ânodos de sacrifício como método para o retardo da degradação e consequentemente mais confiabilidade do sistema.
dc.description.abstract2This work addresses the inspection of a fire protection system (FPS) in a residential building located in the Costa e Silva neighborhood in Mossoró, RN, based on a real failure case which, in condominium, the system was activated during a fire in one of the apartaments. The main objective was to identify the causes of the system malfunction by verifying the existence of corrosion in the pressurized water network and its components such as the pump and the piping. To provide stronger evidence in the results, a qualitative and quantitative analysis was carried out to detect the presence of iron ions and iron oxides (Fe₂O₃) in water samples collected from the hydrant network, confirming the occurrence of internal corrosion in the pipes. As a result, the factors that led the system to fail were indentified, and corrective and preventive actions were implemented, such as maintenance of damage equipament, optimization with the installation of pump activation indicators, level sound alarms, and the implementation of periodic tests to verify the systems availability. The conclusion of the study brought material benefits, such as the restoration of the FPS full functionality, and intangible benefits, such as the knowledge acquired during the study. It also highlighted the importance of regular inspections of FPS systems and suggested futher research for the future adoption of sacrificial anodes as a method to delay degradation and consequently increase the reability of the system.
dc.description.physical50 f.
dc.format.mimetypepdf
dc.identifier.bibliographicCitationSILVA, Victor Esaú Carlos da. Avaliação das condições de integridade e disponibilidade do sistema de combate a incêndio de um condomínio residencial após falha: corrosão na rede de hidrantes e funcionalidade do sistema de recalque. 2025. Trabalho de Conclusão de Curso (Bacharelado em Ciência e Tecnologia) - Universidade Federal Rural do Semi-Árido, Mossoró, 2025.
dc.identifier.urihttps://repositorio.ufersa.edu.br/handle/prefix/13851
dc.language.isopt_BR
dc.publisher.centerCentro de Ciências Exatas e Naturais - CCEN
dc.publisher.countryBrasil
dc.publisher.initialsUFERSA
dc.publisher.institutionUniversidade Federal Rural do Semi-Árido
dc.rightsinfo:eu-repo/semantics/openAccess
dc.rights.holderUFERSA
dc.rights.licenseCC-BY-SApt_BR
dc.rights.licenseAttribution-ShareAlike 3.0 Brazilen
dc.rights.urihttp://creativecommons.org/licenses/by-sa/3.0/br/
dc.subject.cnpqCIENCIAS EXATAS E DA TERRA::CIENCIA E TECNOLOGIA
dc.subject.keywordCorrosão
dc.subject.keywordIncêndio
dc.subject.keywordRede de hidrantes
dc.subject.keywordTubos galvanizados
dc.subject.keywordCorrosion
dc.subject.keywordFire
dc.subject.keywordHydrant network
dc.subject.keywordGalvanized pipes
dc.titleAvaliação das condições de integridade e disponibilidade do sistema de combate a incêndio de um condomínio residencial após falha: corrosão na rede de hidrantes e funcionalidade do sistema de recalque
dc.title.alternativeEvaluation of the integrity and availability conditions of a residential condominium firefighting system after failure: corrosion in the hydrant network and functionality of the pumping system
dc.typeinfo:eu-repo/semantics/bachelorThesis

Arquivos

Pacote original

Agora exibindo 1 - 1 de 1
Carregando...
Imagem de Miniatura
Nome:
VictorECS_MONO.pdf
Tamanho:
2,41 MB
Formato:
Adobe Portable Document Format

Licença do pacote

Agora exibindo 1 - 1 de 1
Carregando...
Imagem de Miniatura
Nome:
license.txt
Tamanho:
1,58 KB
Formato:
Item-specific license agreed upon to submission
Descrição: